Circuit Breaker Analyzer
The ZWKC-G2 is a comprehensive mechanical characteristic tester designed for high-voltage circuit breakers.
It tests 12 metal contacts simultaneously, integrating a DC20~270V power supply for efficient field testing of vacuum, SF6, and oil switches.
Product Overview
The ZWKC-G2 High Voltage Circuit Breaker Analyzer is precision-engineered to evaluate the mechanical dynamic characteristics of high-voltage circuit breakers, including vacuum, SF6, and oil types.
By offering comprehensive measurements of opening/closing time, speed, bounce, and synchronization, it provides essential diagnostic data to ensure the reliable operation and safety of electrical power systems.
Key function and feature:
- Suitable for domestic and foreign SF6 switches, GIS, vacuum switches, and oil switches, delivering versatile diagnostic capabilities for substations and electrical test sites.
- Features a built-in DC20~270V adjustable power supply supporting up to 20A, eliminating the need for an on-site secondary power source and supporting internal trigger operation safely.
- Capable of measuring 12 metal contact fractures, 6 main fractures, and 6 auxiliary fractures concurrently, providing comprehensive time, speed, and bounce data in a single operation.
- Equipped with both linear and 345° rotary sensors with universal brackets for simple, rotation-blind-spot-free mounting on various breaker types and moving contacts.
- Utilizes a 7-inch color screen clearly visible under sunlight, coupled with built-in storage for 100 sets of test data, USB data transmission, and a high-speed thermal printer for immediate on-site reporting.
Technical Details
| Parameter | Specification |
|---|---|
| Model | ZWKC-G2 |
| Power Supply | AC 220V ±10%, 50Hz ±10% |
| DC Power Output | DC20~270V adjustable, ≤20A (short time) |
| Time Measurement Range | 1ms~10000ms |
| Time Accuracy (within 200ms) | 0.05% ± 0.1ms |
| Velocity Measurement Range | 0.01~20.00 m/s (0.1mm sensor) |
| Linear Sensor Range | 0~50mm (optional up to 1000mm) |
| Rotary Sensor Range | 0~345° |
| Operating Temperature | -20°C~+50°C |
| Ambient Humidity | ≤90% RH |
Model Selection Guide
| Item NO. | Max Current | Measuring Range | Main Features | Recommended Application |
|---|---|---|---|---|
| GDZR-10A | 10A | 100μΩ - 20KΩ | Portable, built-in discharge alarm | Small to medium distribution transformers |
| GDZR-20A | 20A | 10μΩ - 10KΩ | High-speed testing, heat dissipation | Medium-sized power transformers |
| GDZR-40A | 40A | 1μΩ - 2KΩ | Dual-channel measurement, high current | Large-scale power transformers |
| GDZR-40A | Three-Phase 10A | 100μΩ - 10KΩ | Three-phase simultaneous measurement | Yn-type transformers, time-saving |
Recent Work



Parts List
| Item NO. | Max Current | Measuring Range | Main Features | Recommended Application |
|---|---|---|---|---|
| GDZR-10A | 10A | 100μΩ - 20KΩ | Portable, built-in discharge alarm | Small to medium distribution transformers |
| GDZR-20A | 20A | 10μΩ - 10KΩ | High-speed testing, heat dissipation | Medium-sized power transformers |
| GDZR-40A | 40A | 1μΩ - 2KΩ | Dual-channel measurement, high current | Large-scale power transformers |
| GDZR-40A | Three-Phase 10A | 100μΩ - 10KΩ | Three-phase simultaneous measurement | Yn-type transformers, time-saving |
Product Video
Discover how the ZWJD111E BDV Tester simplifies insulating oil diagnostics.

Certificate
Frequently Asked Questions
Contact our engineers for technical support and application guidance.
The instrument is designed to test a wide range of high-voltage circuit breakers, including domestic and foreign SF6 switches, GIS combination electrical appliances, vacuum switches, and oil switches.
No, the ZWKC-G2 features an integrated machine operation power supply providing an adjustable DC20 to 270V output. This allows you to perform closing and opening tests without a site secondary power source.
Yes, it accurately measures the opening and closing times of 12 natural switching contacts simultaneously, calculating the time difference between different periods and three-phase synchronism.
For vacuum switches, the included linear sensor is typically attached to the vertical conductive rod (moving contact) using a magnet and secured with a universal bracket. Ensure the electronic ruler is perpendicular to the moving contact before testing.
Related Products